FAQs Pre-insulated pipes

Answer
Yes, if the pipes are not exposed to mechanical stress.

Need more help
Click here
Answer
Normally bending the pipe at a 90° angle is sufficient – this is possible due to the low bending radius. In single instances where bigger dimensions are used, increasing the depth of the pipe trench at the required end is recommended.

Need more help
Click here
Answer
No, since the length extension caused by warming of the soil, is fully compensated for by the pipe insulation.

Need more help
Click here
Answer
Yes. Due to the EVAL protection layer, the heating pipes are diffusion tight in compliance with German DIN 4726.

Need more help
Click here
Answer
A sand layer free of stones is mandatory. The granulation level of the sand should be 0- 2/3 mm. Sharp or sharp-edged items in the trench must be removed in any case. Careful embedding of the pipe into the trench (at a distance of at least 10 cm above and underneath the pipe coating + the distance to the trench walls) has a decisive influence on the durability of the pipe coating. When calculating the minimal covering layer, future building operations (over the entire life time) and possible subsequent damages must be taken into consideration. The filling material must be compressed in layers (if the coverage >500 mm, mechanically). Before filling up the trench, the warning indication must be mounted.
When covering ranges between h=0.5 metres up to a maximum of 6 metres, Uponor Ecoflex jacket pipes can bear soil and traffic loads of SLW 60. The required static verification is listed under regulation ATV-DVWK-A127 currently governing soil-embedded pipes. The verification is required for special mounting conditions only.

Need more help
Click here
Answer
The heat loss is influenced by various factors for which reason we have integrated the respective diagrams into our technical guideline for pre-insulated pipes.

Need more help
Click here
Answer
No, Aqua Twin pipes offer the solution of a hot water and circulation pipe within a single jacket pipe. If a single pipe is used as a cold water supply line, it may warm up and therefore favour bacterial growth.

Need more help
Click here
Answer
The jacket material of a pre-insulated pipe is UV resistant. For this reason, we do not see any problem in mounting the pipe ex-trench. Please ensure that the open pipe ends are not exposed to solar radiation, since the pipe inliner is not UV resistant.

Need more help