Fill the BIM cart from the product catalogue

GF Uponor RS adapter S-Press

- Made of tin-plated DR brass
- Fits to all RS2 or RS3 base parts.

GF Uponor RS adapter S-Press

Item details

GF Uponor RS adapter S-Press 75-RS2
GF Uponor RS adapter S-Press 90-RS3
GF Uponor RS adapter S-Press 110-RS3

Documents

Technical information
12 KB1142162

TI MLC tap water heating UK 1142162

Installation Manual
2 KB1044657

Installation Manual RS (1044657)

Installation Manual
1 KB1187006

Installation Manual PE-Xa (1187006)

Approval Certificate
295 B1120771

UPONOR CER S-Press SYS MECH WRAS 2101908 GB EN (1120771)

Approval Certificate
409 B1013450

UPONOR SAMPLE MLC PIPE WHITE 50X4,5 LENGTH 30CM

Approval Certificate
409 B1013402

UPONOR SAMPLE MLC PIPE WHITE 32X3 LENGTH 30CM (1013402)

About

Specification

- Tin-plated brass
- Fixed press sleeve with inspection windows
- Stop ring
- Colour code
- Test safety
- Male and female threads to BS EN 10226-1

Application

Tested/approved according to BS EN ISO 21003 Multilayer
piping systems for hot and cold water installations inside
buildings for application class 1,2,4,5/10bar

Domestic water services: The permanent operating
temperature from 20°C to 70°C at a maximum permanent
operating pressure of 10 bar. The short-term malfunction
temperature is 95°C for a period of 100 hours in the operating
life time.

Domestic cold water services : where the water temperature
does not exceed 20°C at a maximum permanent operating
pressure of 16bar.

Heating: The permanent operating temperature ranges up
to 80°C at a maximum permanent operating pressure of 10 bar.
The short-term malfunction temperature is 100°C for a period
of 100 hours in the operating life time.

Certification

UK Reg4 approval
- WRAS or
- KIWA
To meet the requirements of the Water Supply (Water Fittings) Regulations 1999

Product drawings

1029126_ZMD
1029126
145 B
1029127_ZMD
1029127
145 B
1029128_ZMD
1029128
145 B
1029126_REN
1029126
89 B
1029128_REN
1029128
89 B