Uponor S-Press PLUS mount. Unit sound p.
- Tap elbow assembly - Installed on mounting angle with rotation protection, integrated sound protection and incl. drainage function - Sound protection according to VDI 4100 SST 1 / SST 2 / SST 3* (* for drywall installation) and DIN 4109 - Drainage of possible leakage water according to DIN 18534
Item details
Documents
Technical manuals
Installation Report MLC leak test report TW water (1120119)
About
Specification
- Unique press indicator foil - Fast 3-step installation (press without bevel) - Innovative QR code for immediate digital access - Colour coded - Fixed press sleeve with inspection windows - Precise jaw location - Fast diameter recognition - Accurate test safety function - 100% backward compatible with existing Uponor components - Flow rate optimized fitting body
Application
Tested/approved according to BS EN ISO 21003 Multilayer piping systems for hot and cold water installations inside buildings for application class 1,2,4,5/10barDomestic water services: The permanent operating temperature from 20°C to 70°C at a maximum permanent operating pressure of 10 bar. The short-term malfunction temperature is 95°C for a period of 100 hours in the operating life time. Domestic cold water services : where the water temperature does not exceed 20°C at a maximum permanent operating pressure of 16bar.Heating: The permanent operating temperature ranges up to 80°C at a maximum permanent operating pressure of 10 bar. The short-term malfunction temperature is 100°C for a period of 100 hours in the operating life time.
Certification
UK Reg4 approval - WRAS or - KIWA to meet the requirements of the Water Supply (Water Fittings) Regulations 1999