Fill the BIM cart from the product catalogue

Uponor S-Press adapter male thread

- Made of tin-plated brass
- Fast installation with easy bevel and without need for calibration
- Inspection windows on press sleeve
- Colour code

Uponor S-Press adapter male thread

Item details

Uponor S-Press adapter male thread 40-R1 1/4"MT
Uponor S-Press adapter male thread 40-R1 1/2"MT
Uponor S-Press adapter male thread 50-R1 1/2"MT
Uponor S-Press adapter male thread 50-R2"MT
Uponor S-Press adapter male thread 63-R2"MT
Uponor S-Press adapter male thread 75-R2 1/2"MT

Documents

Product Information
259 B1142159

PI MLC tap water heating UK 1142159

Installation Manual
1 KB1239731

IM Uni Pipe and S-Press system 14-110 INT 1239731 v1

Installation Report
116 B1120119

Installation Report MLC leak test report TW water (1120119)

Approval Certificate
264 B1120771

UPONOR CER S-PRESS SYS MECH WRAS 2101908 GB EN (1120771)

Approval Certificate
836 B1089107

UPONOR CER MLC SYS MECH Lloyds Register 17-20013-2 GB EN (1089107)

Approval Certificate
409 B1013450

UPONOR SAMPLE MLC PIPE WHITE 50X4,5 LENGTH 30CM

Environmental Product Declaration (EPD)
899 B1162876

Uponor EPD S-Press (1162876)

About

Specification

- Tin-plated brass or PPSU
- With fixed press sleeve
- Stop ring
- Colour code
- Test safety
- Male and female threads to BS EN 10226-1

Application

Tested/approved according to BS EN ISO 21003 Multilayer
piping systems for hot and cold water installations inside
buildings for application class 1,2,4,5/10bar

Domestic water services: The permanent operating
temperature from 20°C to 70°C at a maximum permanent
operating pressure of 10 bar. The short-term malfunction
temperature is 95°C for a period of 100 hours in the operating
life time.

Domestic cold water services : where the water temperature
does not exceed 20°C at a maximum permanent operating
pressure of 16bar.

Heating: The permanent operating temperature ranges up
to 80°C at a maximum permanent operating pressure of 10 bar.
The short-term malfunction temperature is 100°C for a period
of 100 hours in the operating life time.

Certification

UK Reg4 approval
- WRAS or
- KIWA
To meet the requirements of the Water Supply (Water Fittings) Regulations 1999

Product drawings

1032895_REN
1032895
389 B
1032896_REN
1032896
136 B
1046901_REN
1046901
389 B
1046901_REN
1046901
136 B
1046902_REN
1046902
165 B
1046905_REN
1046905
35 B
1032896_ZMD
1032896
132 B
1046901_ZMD
1046901
132 B
1046902_ZMD
1046902
132 B
1046905_ZMD
1046905
132 B
1032896_LAB
1032896
115 B
1046901_LAB
1046901
115 B
1046902_LAB
1046902
115 B
1046905_LAB
1046905
115 B