Product data collection and use notice
This notice is to inform you about data collected by the device. For personal data, please see Privacy Statement.
Device Name: Hycleen Flush
Manufacturer: Georg Fischer
Key information: Hycleen Flush valves collect data points from the drinking water lines and use them to automate water flushing safely and precisely, thereby playing a key role in keeping drinking water hygienically safe in cold and hot water pipes. These data points include temperature measurements on several pipes within the drinking water, where the Hycleen Flush is installed. In addition to the temperature measurements, the user can add one or two additional sensors based on 4-20mA analog input for monitoring purposes, E.g. one flow and drainage monitoring to check stagnation and avoid damage in case drainage is stuck.
Data is collected continuously on a 5-minute interval and stored within the Hycleen Flush valve.
DATA TYPES AND FORMAT:
- Data type: Temperature, l/h, 0/1, 4-20mA
- Format: csv
- Estimated Volume: 10KB per day
- Periodic data collection (every 5 minutes)
- On-device storage
- Retention period: 1 year
- Users may access their data through Hycleen Flush Bluetooth app. They can visualize all collected data from Hycleen Flush devices on the app.
- In addition, the Users may read current datapoints via Modbus RTU protocol.
- Quality of service on access to this data is guaranteed by industry standard best practices regarding resilience, scalability, availability, privacy and security for embedded devices.
- How to delete: User data and building information will be deleted by factory reset of the Hycleen Flush valve.